InspectOS inspection report · 2026

What InspectOS engineers find in Portuguese homes

2026 data from InspectOS inspections: pre-purchase, damp, new homes and gas.

InspectOS engineers rated at least one item non-conform in 84% of the homes they inspected before purchase in 2026. The electrical installation, and walls, windows and finishes, were flagged most often; presence of moisture was the single item flagged most.

Published:

Period
March to November 2026
Coverage
Mainland Portugal, most often the Lisboa and Porto districts
Services
Pre-purchase, damp, new-build and gas inspections
Who inspects
Engineers registered with the Ordem dos Engenheiros on the building inspections. Gas by a DGEG-recognised EIG.

1 · Key findings

Six findings from 2026

  • 84%

    of 2026 pre-purchase inspections had at least one item rated non-conform by an InspectOS engineer.

  • 66%

    of 2026 pre-purchase inspections had three or more items rated non-conform.

  • 53%

    of 2026 pre-purchase inspections flagged the presence of moisture, the checklist item flagged most often.

  • 66%

    of 2026 InspectOS moisture inspections recorded water getting in from outside, the cause recorded most often, ahead of rising damp and condensation.

  • 21%

    of 2026 pre-purchase inspections recorded a structural defect or recommended a specialist structural check.

  • Most

    new homes InspectOS inspected before purchase in 2026 had at least one item rated non-conform and needing correction.

2 · Familiar problems

Problems most people in Portugal already know

People in Portugal often blame condensation for damp. In 2026 InspectOS moisture inspections, water getting in from outside was the cause recorded most often (66%), and condensation was never the only one.

Damp walls in winter, mould behind the wardrobe, water through the ceiling after heavy rain. Most people in Portugal know these from their own home or a friend's. Each problem below sits next to the national figure and what InspectOS engineers recorded.

  1. Damp and mould every winter

    What people describe

    Mould back on the window frames a few days after cleaning. Clothes in the wardrobe that smell of damp. A dehumidifier running all winter.

    In Portuguese: humidade nas paredes · casa cheia de humidade · bolor no teto · manchas pretas · o bolor voltou

    National figure

    INE's 2025 survey found 32.1% of people in Portugal living in a home with a leaking roof, damp walls or floors, or rot in window frames or floors. In 2023, Portugal's share was 29.0%, second in the EU after Cyprus; the EU average was 15.6%.

    INE, Survey on Income and Living Conditions (ICOR) 2025; Eurostat, EU-SILC 2023 (ilc_mdho01)

    What InspectOS engineers recorded

    Wherever InspectOS engineers recorded mould in 2026, they also found water getting in: rising damp, water from outside or a leak. Before purchase, presence of moisture was flagged in 53% of inspections, more than any other checklist item.

    Moisture inspection
  2. Water getting in when it rains

    What people describe

    Water through the ceiling after heavy rain. Buckets on the floor. A roof or terrace leak that nobody fixes.

    In Portuguese: chove dentro de casa · entra água pelo telhado · goteira no teto · infiltração no terraço

    National figure

    Leaking roofs are part of the national figure in the first problem above.

    What InspectOS engineers recorded

    Water getting in from outside was the cause of damp InspectOS engineers recorded most often, in 66% of 2026 moisture inspections. It points to the building envelope: roofs, terraces, facades, window frames and walls against the ground.

    Moisture inspection
  3. It is not just condensation

    What people describe

    Windows dripping every morning. Laundry that never dries. And the advice to just open the windows.

    In Portuguese: condensação nas janelas · vidros molhados de manhã · a roupa não seca

    National figure

    Condensation sits inside the national damp figure above, with no separate national figure.

    What InspectOS engineers recorded

    Condensation was never the only cause: wherever InspectOS engineers recorded it in 2026, another source of water was present as well. In 66% of damp inspections, the damp had more than one source at the same time.

    Moisture inspection
  4. Damp low on ground-floor walls

    What people describe

    A damp band along the bottom of the walls. White salt marks. Skirting boards that swell and come away.

    In Portuguese: humidade no rés-do-chão · humidade a subir pela parede · salitre · rodapés inchados

    What InspectOS engineers recorded

    Engineers call this rising damp: water from the ground drawn up through the wall. InspectOS engineers recorded it in 41% of 2026 moisture inspections, second only to water getting in from outside.

    Moisture inspection
  5. Damp back after a fresh coat of paint

    What people describe

    Mould painted over every year and back by the next winter. A smell of fresh paint at the viewing. One wall newly painted when the rest are not.

    In Portuguese: pintaram por cima do bolor · cheira a tinta fresca · vícios ocultos

    What InspectOS engineers recorded

    In 14% of 2026 InspectOS damp inspections, engineers found active moisture at spots that had already been repaired or repainted.

    Moisture inspection
  6. Cracks in the walls

    What people describe

    A crack filled and painted over before the viewing. The question every buyer asks: is this one serious?

    In Portuguese: fissuras na parede · rachas · racha a aumentar

    National figure

    In the 2021 Census, 35.8% of buildings in Portugal needed repair: 21.8% light, 9.4% medium and 4.6% major.

    INE, Census 2021

    What InspectOS engineers recorded

    InspectOS engineers recorded a structural defect or recommended a specialist structural check in 21% of 2026 pre-purchase inspections.

    Pre-purchase inspection
  7. The building, not just the flat

    What people describe

    A roof or facade leak that nobody repairs. Condominium minutes full of disputes. And the question of who pays.

    In Portuguese: obras no condomínio · telhado do prédio · fachada · quem paga?

    What InspectOS engineers recorded

    The exterior walls and facade were rated non-conform in 29% of 2026 pre-purchase inspections. In an apartment, the facade is a common part shared with the other owners.

    Condominium common areas inspection
  8. New, but not finished

    What people describe

    Problems in the first week in a brand-new home. A builder who stops answering.

    In Portuguese: casa nova com defeitos · construtora não resolve

    What InspectOS engineers recorded

    Most new homes InspectOS inspected before purchase in 2026 had at least one item rated non-conform and needing correction.

    Snagging inspection
  9. Built work not on the papers

    What people describe

    An enclosed balcony with no licence. An extension the floor plan does not show.

    In Portuguese: obras ilegais · marquise sem licença · não bate com a planta

    What InspectOS engineers recorded

    InspectOS pre-purchase inspections in 2026 recorded building work the documents did not show: extensions, added rooms, a mezzanine and a detached annex. These are cases, not a rate.

    Pre-purchase inspection
  10. Cold homes

    What people describe

    Colder inside than outside in winter. Coats on indoors. No central heating.

    In Portuguese: casas frias · mais frio dentro do que fora · sem isolamento

    National figure

    INE's 2025 survey found 15.6% of people in Portugal could not afford to keep their home adequately warm.

    INE, Survey on Income and Living Conditions (ICOR) 2025

    Context: no InspectOS figure

Where people describe it most

Across Reddit, X and Facebook, people describe these problems mostly in winter, with short spikes after storms. By region, the themes differ.

Porto and the North
Cold homes, mould and damp.
Lisbon city and metropolitan area
Mould, cold homes, old rentals and roof leaks.
Sintra, Cascais, Oeiras and Ericeira
Damp and mould, with a dehumidifier in many rooms.
Algarve
Damp, mould and leaks after heavy rain.
Setúbal peninsula
Damp, leaks and flooding in storms.

National figures come from INE and Eurostat and carry their source and year. What people describe is paraphrased from public online discussions on Reddit, X and Facebook; it shows what people talk about, not how common a problem is. Figures about InspectOS inspections use only InspectOS reports.

3 · Now

Winter: water coming in from outside

InspectOS engineers recorded water getting in from outside in 66% of their 2026 moisture inspections, more often than any other cause of damp.

Rain enters through roof coverings, flashings, terraces, facades and window frames. It often travels inside the construction and appears some distance from where it entered. A stain on a ceiling can come from a terrace or a roof valley metres away.

Searches in Portugal for roof leaks ("infiltração telhado") rise every autumn and peak between November and March (Ahrefs Keywords Explorer, January 2024 to November 2026).

What the engineers recorded

  • In 66% of 2026 damp inspections, the damp had more than one source at the same time.
  • Condensation was never the only cause: wherever it was recorded, another source of water was present as well.
  • InspectOS engineers recorded mould in 52% of 2026 damp inspections. Wherever they did, they also found water getting in: rising damp, water from outside or a leak.
  • In 14% of 2026 damp inspections, engineers found active moisture at spots that had already been repaired or repainted.
  • In 52% of 2026 damp inspections, thermal imaging located anomalies that moisture-meter readings then confirmed.
  • Before purchase, InspectOS engineers flagged waterproofing in 32% of 2026 inspections and ceilings in 29%.

Case · condominium, 2026

Water entering from the outdoor areas above a garage had come back through walls that had already been repaired. After prolonged damp, the reinforcement of the garage ceiling slab was exposed.

Moisture inspection

4 · Before purchase

The condition of homes before purchase

InspectOS engineers rated at least one item non-conform in 84% of 2026 pre-purchase inspections, and flagged at least one item in 95%.

Every pre-purchase inspection rates the same standard checklist, from foundations to fire safety. "Flagged" means rated as requiring review or non-conform. The table shows how often each item was flagged, and how often it was non-conform.

  • The electrical installation was flagged in 76% of 2026 pre-purchase inspections, and walls, windows and finishes in 71%.
  • The items flagged most often were presence of moisture, interior walls, window frames, shower bases and sockets.
  • The exterior walls and facade were rated non-conform in 29% of inspections. In an apartment, the facade is a common part shared with the other owners.
  • A home with no flagged item was the exception. A buyer should expect a list of corrections before signing.
Areas with at least one item flagged

Share of 2026 pre-purchase inspections

  1. Electrical installation76%
  2. Walls, windows and finishes71%
  3. General condition and safety66%
  4. Moisture63%
  5. Insulation and ventilation58%
  6. Water and drainage58%
  7. Structure21%
Share of 2026 pre-purchase inspections in which each item was flagged (requires review or non-conform), and in which it was non-conform.
ItemFlaggedNon-conform
Structure21% of inspections with at least one item flagged
Foundations and main structure5%3%
Beams and columns8%5%
Slabs13%5%
Walls, windows and finishes71% of inspections with at least one item flagged
Interior walls45%21%
Exterior walls and facade37%29%
Window frames and glazing45%24%
Floors24%16%
Ceilings29%21%
Moisture63% of inspections with at least one item flagged
Presence of moisture53%39%
Condensation8%5%
Waterproofing32%11%
Insulation and ventilation58% of inspections with at least one item flagged
Wall insulation29%0%
Roof insulation24%3%
Thermal bridges11%3%
Natural ventilation13%5%
Mechanical ventilation32%11%
Electrical installation76% of inspections with at least one item flagged
Main electrical panel21%13%
Earth connection34%13%
General wiring18%8%
Sockets39%26%
Switches26%5%
General lighting34%8%
Emergency lighting26%13%
Water and drainage58% of inspections with at least one item flagged
Water supply network26%5%
Water quality18%0%
Taps and valves34%18%
Interior drainage18%0%
Sewage piping24%5%
Traps and drains16%8%
Toilets and cisterns32%13%
Shower bases and baths42%26%
General condition and safety66% of inspections with at least one item flagged
General condition34%16%
General maintenance26%11%
Regulatory compliance18%8%
Fire safety32%18%
Accessibility5%0%
Pre-purchase inspection

5 · Paper vs reality

When the building does not match its documents

InspectOS pre-purchase inspections in 2026 recorded building work the documents did not show: extensions, added rooms, a mezzanine and a detached annex.

  • A mezzanine in a property whose approved area was smaller.
  • Later alterations that the municipal record identified as unlicensed.
  • A former pergola enclosed to create a bedroom with a bathroom. The engineer recorded settlement of the foundation in that area, with related cracking, linked to the loads the works had added.

Example: a house licensed in 1965

Four documents describe the 1965 house: one storey, 4 divisions, 55 m², no annex. On site, the house had grown.

ItemOn paperWhat we foundResult
Storeys1 storeycaderneta, certidão, 1965 plan1 storeysingle-storey throughoutMatches
Rooms4 divisionstwo bedrooms, kitchen, dining room, plus bathroom6 added spacestwo bedrooms, hall, kitchen, WC, storage roomDiffers
KitchenIn the original house1965 planMoved to an additionthe old kitchen is now a living roomDiffers
AnnexNone recordedárea bruta dependente 0 m²Detached annexon the plot, in poor conditionDiffers
Gross area55 m²área bruta privativaTo be measureda survey on the same basis settles itNot comparable yet

From a 2026 InspectOS pre-purchase inspection in southern Portugal. Address, names and exact dates generalised.

What the law says about a mismatch

  • Since 1 October 2026, every deed transferring a building must record the status of its título urbanístico: presented, held but not shown, or not held. Without that mention, the deed is anulável.

    DL 108/2026, rectified by Declaração de Retificação n.º 29-A/2026/1

  • A property can still be sold without a título urbanístico. The deed records the title's status; the notary records that status and does not verify the title itself.

    DL 108/2026, rectified

  • Works carried out without the required title carry fines of €500 to €200,000 for individuals.

    RJUE, art. 98.º n.º 1 r) and n.º 2

  • Using a building without the required title, or for another use, carries fines of €500 to €100,000 for individuals.

    RJUE, art. 98.º n.º 1 d) and n.º 4

  • The câmara municipal can order the total or partial demolition of such works. Demolition can be avoided if the works can be legalised.

    RJUE, art. 106.º n.º 1 and 2

  • In a private sale, the buyer must report a defect within one year of finding it and sue within six months of that report, all within five years of delivery. The buyer carries the burden of proof.

    Civil Code, arts. 913.º, 916.º n.º 3, 917.º and 342.º n.º 1

An engineer's comparison of the documents with the building, made before signing, is the evidence a buyer's lawyer works from.

Pre-purchase inspection

6 · New homes and gas

New homes and gas installations

Most new homes InspectOS inspected before purchase in 2026 had at least one item rated non-conform and needing correction.

  • Recording these items before handover gives the buyer a documented list for the builder.
  • A DGEG-recognised EIG approved most of the gas installations it inspected in 2026 at the first inspection.
  • A pending result from the EIG means the non-conformities have to be corrected and the installation inspected again before it can be approved.
Snagging inspection

7 · Method

How this report was built

Data

Each property was inspected on site. On the building inspections, the work was done by an engineer registered with the Ordem dos Engenheiros. For gas, a DGEG-recognised EIG carries out the inspection and issues the certificate, and the InspectOS report is the bilingual document prepared from the EIG's report. Every 2026 report was coded by hand against a fixed codebook and checked against the report text. Each figure was recomputed from the coded data.

Figures

Percentages are given for the pre-purchase and moisture inspections. Smaller groups, such as new homes and gas installations, are described in words. Locations are stated at district level.

Cite this report

InspectOS, 2026 Inspection Report, November 2026. https://www.inspectos.pt/en/inspection-data

These figures come from a random sample of inspections carried out by InspectOS in 2026. They represent part of our inspection records, not all of them.

Inspections in mainland Portugal